Share This Page

HW208A: 15kV Shielded 133%, EPR, PVC - Aluminum

Application

For use in aerial, direct burial, cable tray, conduit, and underground duct installations as permitted by the National Electric Code. The cable is capable of operating continuously with a conductor temperature not to exceed 105C for normal operation, 140C for emergency overload conditions, and 250C for short circuit conditions. It is rated at 15,000V with 133% insulation level (ungrounded system). Maximum sidewall perssure is 1000 lbs.

Conductor

  • Aluminum alloy 1350-H19, compressed Class B stranding, or unilay-compressed per ASTM B231, or combination unlay (19 wires) per ASTM B78.

Conductor Shield

  • Extruded semi-conducting thermoset polymeric layer over the conductor, applied in tandem and firmly bonded to the insulation

Insulation

  • Ethylene propylene rubber (EPR) with a nominal thickness of 0.220"

Insulation Shield

  • Extruded layer of semi-conducting thermosetting material. Over this layer will be applied a helically wrapped 5-mil copper tape shield with minimum 25% overlap

Jacket

  • Black sunlight resistant PVC per ICEA S-97-682, with average thickness in accordance to Table 7-3 of ICEA

Additional Standards

  • UL 1685 - 1/0 AWG and larger, UL-CT Flame Exposure Test
  • UL 1072 - Medium Voltage Power Cables
  • ICEA S-93-639
  • ICEA S-97-682
  • IEEE 1202/FT4

Browse HW208A: 15kV Shielded 133%, EPR, PVC - Aluminum Products