For use in aerial, direct burial, cable tray, conduit, and underground duct installations as permitted by the National Electric Code. The cable is capable of operating continuously with a conductor temperature not to exceed 1050C for normal operation, 1400C for emergency overload conditions, and 2500C for short circuit conditions. It is rated at 15,000V
with 133% insulation level (ungrounded system). Maximum sidewall pressure is 1000 lbs. This cable does not require the use of pulling lubricant.
8000 series aluminum compact conductor in accordance with ASTM specs B800and B801 and ICEA part 2, Section 2.1 and 2.5.
Ethylene propylene rubber (EPR) with a nominal thickness of 0.220
Extruded layer of semi-conducting thermosetting material which shall be identified as being semi- conducting. Over this layer will be applied a helically wrapped 5-mil copper tape with 25% overlap.
Sunlight resistant PVC per ICEA S-97-682, with average thickness in accordance to Table 7-3 of ICEA.
UL 1685 – 1/0 and larger, UL-CT Flame Exposure Test
For use in aerial, direct burial, cable tray, conduit, and underground duct installations as permitted by the National Electric Code. The cable is capable of operating continuously with a conductor temperature not to exceed 105°C for normal operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions. It is rated at 15,000V with 133% insulation level (ungrounded system). Maximum sidewall pressure is 1000 lbs. This cable does not require the use of pulling lubricant.
HWC also specializes in hard-to-find specialty items. The HWC team is always concerned with filling customers' orders as properly and efficiently as possible. And if it's not in stock, HWC will get it- no problem! Get A Quote
With over 30,000 products sold annually, Houston Wire & Cable provides its customers with knowledgeable market and product application experts, standard same-day shipments, 99.99% order accuracy and on-time delivery, and 24/7/365 service.